Tongxing’s ceiling & floor indoor units are designed for VRF/VRV central air conditioning systems in commercial and large residential applications. With DC-inverter compressors and low-noise fan motors, these ceiling/floor-mounted units deliver stable cooling/heating, advanced machine-learning air-filter monitoring, multi-step vertical swing for even airflow, and flexible 2-way installation options. Available in multiple capacities (3.6–80 kW) and refrigerant options (R410A / R32), they are ideal for hotels, shopping malls, schools, hospitals and other venues requiring energy-efficient, quiet indoor climate control. Download datasheet for model specs, sound levels, piping sizes, and packing details — contact us for custom configurations and OEM options.

Discuss your project

Product specifications.

Model nameMIH36DLHN18MIH45DLHN18MIH56DLHN18MIH71DLHN18MIH80DLHN18
Power supply1-phase, 220-240V, 50/60Hz
CoolingCapacitykW3.64.55.67.18
kBtu/h12.315.419.124.227.3
Power InputW1624404256
HeatingCapacitykW456.389
kBtu/h13.717.121.527.330.7
Power InputW1624404256
Airflow rate3m3/h564/539/ 514/492/ 467/445/424712/674/ 637/603/ 565/531/500927/883/ 840/794/ 751/707/6651128/1062 /1024/926/ 860/791/7291300/1218/ 1138/1057/ 982/904/824
Sound pressure leveldB(A)32/30/29/28/ 27/26/2536/35/34/33/ 32/31/3043/41/40/38/ 36/34/3343/40/39/37/ 35/34/3345/44/42/40/ 38/36/34
Sound power leveldB(A)43/42/40/39/ 38/38/3747/45/45/43/ 42/41/4054/53/51/50/ 48/47/4554/53/52/51/ 49/48/4855/53/51/50/ 49/46/44
UnitNet dimensions (W¨H¨D)1069*674*2341069*674*2341069*674*2341284*674*2341284*674*234
Packed dimensions (W¨H¨D)1190*755*3131190*755*3131190*755*3131405*755*3231405*755*323
Net/Gross weight24.7/29.524.7/29.524.7/29.529.8/34.829.8/34.8
Refrigerant typeR410A/R32R410A/R32R410A/R32R410A/R32R410A/R32
Pipe connectionsLiquid/Gas pipemm6.35/12.76.35/12.76.35/12.79.52/15.99.52/15.9
Drain pipemmOD 25OD 25OD 25OD 25OD 25
HP22242628
Power supplyV/N/Hz380-415/3/50(60)
CoolingCapacitykW61.5677378.5
kBtu/h209.8228.6249.1267.9
Power InputW17192124
EER3.433.523.473.27
HeatingCapacitykW697581.587.5
kBtu/h235.4255.9278.1298.6
Power InputW17.6192124.2
COP3.913.953.883.62
CompressorsTypeDC inverter
Quantity2
Airflow ratem3/h22000215002150029000
RefrigerantR410A
Sound pressure leveldB(A)62626263
Net dimensions (W×H×D)mm1340×1760×8251340×1760×8251340×1760×8251880×1760×825
Packed dimensions (W×H×D)mm1410×1945×8901410×1945×8901410×1945×8901935×1945×890
Net weightKg295315315373
Gross weightKg315335335403
Ambient temp. operation rangeCooling-15 to 55
Heating-30 to 30

Product Description

Digital display on/off: Indoor unit displays can be deactivated at night, creating a darker environment for sleep.

Quiet operation: The DC-powered fan motor and water pump enable quieter, more energy-efficient operation compared to AC-powered units, ensuring a tranquil and comfortable indoor environment.

Air filter monitoring: The built-in machine learning technology can detect the real-time resistance of the filter screen. It displays the degree of blockage on the controller, ranging from 10% to 100%, to alert technicians when maintenance is required.

Multi-step vertical swing: 5-step, louver vertical-swing feature with automatic setting, uniformly distributes airflow at a wide 35-65· angle for more consistent temperature control.

Parameter

Usage Scenario Description

Hotels, shops, schools, shopping malls, hospitals, etc commercial venues of different sizes

Comparison Module

More flexible, 2-way installation; Auto cooling/heating changeover;

Dual-thermistor control

Achieve optimal indoor comfort with this sophisticated VRF Central Air Conditioning System, designed to provide flexible temperature control through ceiling and floor mounted indoor units that adapt to various architectural layouts. The system features digital display controls that can be deactivated during nighttime hours, creating darker sleeping environments while maintaining precise climate management. This advanced VRF Central Air Conditioning System operates with remarkably quiet performance through DC-powered fan motors and water pumps that reduce noise levels while improving energy efficiency compared to conventional AC-powered alternatives. Building owners and facility managers appreciate the intelligent air filter monitoring that utilizes machine learning technology to detect real-time filter resistance and display blockage percentages from 10% to 100%, providing clear maintenance alerts that optimize system performance and indoor air quality.

FAQS

What applications are ceiling & floor indoor units best for?

They are ideal for hotels, retail stores, schools, hospitals and other commercial spaces where flexible installation (ceiling or floor) and low noise are required.

Which refrigerants and capacities are available?

Models support R410A and R32 refrigerants with cooling capacities from ~3.6 kW up to 80 kW (multiple model ranges). See the datasheet for exact model-by-model specs.

How quiet are these units?

These units use DC-inverter fans and water pumps for lower noise. Typical sound pressure levels range from mid-20s to low-40s dB(A) depending on model and fan speed—refer to the spec table on the page.

What special features do they offer?

Features include digital display on/off (night mode), multi-step vertical swing (5-step), ML-based air filter blockage monitoring (10%–100%), and dual-thermistor control for precise temperature regulation.

How do I choose the right capacity for my room?

Select capacity based on room area/volume, insulation, occupancy and heat loads. For accurate selection, provide project details (floor area, ceiling height, windows) so our engineers can recommend the correct model.

View original product specifications ↗

YOUR NEXT PROJECT STARTS HERE

Great spaces.
Start with a conversation.

Let’s build your solution